Product Description
Category: Rigid Cables
- Sub Category: Armoured Cables 1.1 kV
- Type Bet: A2XFY
- Standards: IS: 7098/Pt.-1/1988
Product Features:
- Light Weight
- Good Thermal Properties than PVC Variant
- Good Strength than PVC Variant
- Low Current Leakage than PVC Variant
Construction:
- Class -2 Stranded Aluminium Wire as per IS:8130
- Insulation: XLPE as per IS:7098
- Core ldentification:
- Core: Black / Red /White
- Core: Red, Black
- Core: Red,Yellow, Blue
- Core: Red,Yellow, Blue and Black
- Inner Sheath: PVC ST2 Grade as IS:5831
- Armouring: H.D.Aluminium / G.I. Strip as per wire IS:
- Outer Sheath: PVC ST2 Grade as per IS : 5831
Variants:
Technical Data:
- Insulation Resistance: 1 X 1014 Ohm-CM
- Bending Radius: 12 X OD (OD = Overall Diameter of Cable)
- Voltage Rated: 650 / 1100 Volts
- Test Voltage: a.c.3 kV (rms)
- Temperature Range: 45°C to + 90°C
- Short Circuit Temp.: 250° C
DIMENSIONAL TABLES, POWER CABLES - ALUMINIUM / XLPE / STRIP ARMOUREDI PVC TABLE -1 SINGLE CORE ALUMINIUM CONDUCTOR XLPE INSULATED AND PVC SHEATHED H.D.AL.STRIP ARMOURED CABLES ACCORDING TO IS:7098/PT. 111988
| Core Size | Stranding(Minimum No. of Strands) | Nominal Thickness of Insulation (mm) | Nominal Overall Diameter (mm) | Approx. Weight (kg/km) | Max DC Resistance at 20°C | Current Rating (Amp) |
| SQ MM |
| 1 X 95.0 | 19 | 1.4 | 21 | 560 | 0.32 | 230 |
| 1X 120.0 | 37 | 1.5 | 22 | 660 | 0.253 | 268 |
| 1X 150.0 | 37 | 1.7 | 23 | 750 | 0.206 | 309 |
| 1X 185.0 | 37 | 1.9 | 25 | 900 | 0.164 | 360 |
| 1X 240.0 | 61 | 2 | 27.5 | 1100 | 0.125 | 433 |
| 1X 300.0 | 61 | 2.1 | 30 | 1350 | 0.1 | 501 |
| 1X 400.0 | 61 | 2.4 | 34 | 1725 | 0.0778 | 596 |
| 1X 500.0 | 61 | 2.6 | 37.5 | 2090 | 0.0605 | 693 |
| 1X 630.0 | 91 | 2.8 | 40.5 | 2525 | 0.0469 | 814 |
| 1X 800.0 | 91 | 3.1 | 51.2 | 4519 | 0.0367 | 890 |
| 1X 1000.0 | 91 | 3.3 | 56.7 | 5398 | 0.0291 | 1050 |
Versatile Industrial ApplicationsThis cable is specifically designed for use in a broad spectrum of industrial environments, including underground wiring, power distribution networks, and cable trays. Its mechanical protection ensures longevity even in demanding installations like direct burial and trenches, making it suitable for both indoor and outdoor use in energy infrastructure projects.
Comprehensive Safety and DurabilityThe aluminium XLPE strip armoured cable incorporates state-of-the-art features such as high tensile strength, excellent dielectric stability, and resistance to chemicals, water, oil, and UV rays. Flame retardant and fire-resistant characteristics provide critical safety for industrial sites, while customization of core number and size guarantees adaptability for specific electrical load and project requirements.
FAQs of Al Xlpe Strip Armoured:
Q: How is the Aluminium XLPE Strip Armoured Cable installed and what surfaces is it suitable for?
A: This cable is optimized for direct burial, trenches, and cable trays, ensuring reliable performance in underground and exposed industrial settings. Its strip armoured construction delivers additional mechanical protection, making it suitable for harsh environmental conditions.
Q: What are the key benefits of using XLPE insulation in this cable?
A: XLPE (Cross Linked Polyethylene) insulation offers exceptional heat, moisture, and electrical resistance. It ensures excellent conductivity, long-term durability, and operational reliability, even at elevated temperatures up to 90C.
Q: Where can the cable be utilized in industrial power distribution systems?
A: The cable is ideal for use in industrial electrical networks, power distribution stations, and underground wiring installations, providing robust support for safe and efficient energy transmission.
Q: What safety features does this cable provide against fire and hazardous conditions?
A: This cable is flame retardant and fire resistant, minimizing fire hazards. It also withstands exposure to chemicals, water, oil, and UV rays, ensuring operation in challenging industrial and environmental conditions.
Q: When can the earth continuity conductor be included and how is the length specified?
A: The earth continuity conductor is available upon request for enhanced safety in grounding applications. Cable length and core configurations can be fully customized according to project demands and application needs.
Q: What is the process for marking and how does it benefit identification?
A: Each cables outer sheath is marked or printed as per IS standards, ensuring easy identification, compliance tracking, and streamlined installation processes at industrial sites.